KV Software

PT charts / R-404A

R-404A PT chart

Saturation pressure and temperature for R-404A, from -40 to 150 °F in 2 °F steps, in psig at sea level.

R-404A is R-125 / R-143a / R-134a (44/52/4 wt). It is a near-azeotropic blend with about 0.9 °F of glide, so bubble and dew pressure differ. ASHRAE 34 safety class A1, lower toxicity and no flame propagation.

Superheat and subcooling calculator

Type what your gauges and clamp read for R-404A. Superheat uses the dew point, subcooling uses the bubble point.

Superheat

Enter the suction pressure.

Subcooling

Enter the liquid pressure.

R-404A pressure temperature chart

Temp °FBubble psigDew psig
-404.94.3
-385.95.3
-367.06.3
-348.07.4
-329.28.5
-3010.39.6
-2811.510.8
-2612.812.0
-2414.113.3
-2215.414.6
-2016.816.0
-1818.317.4
-1619.818.9
-1421.320.4
-1222.922.0
-1024.623.6
-826.325.3
-628.027.0
-429.828.8
-231.730.7
033.732.6
235.734.6
437.736.6
639.838.7
842.040.9
1044.343.1
1246.645.4
1449.047.8
1651.550.2
1854.052.7
2056.655.3
2259.357.9
2462.060.7
2664.863.5
2867.866.4
3070.769.3
3273.872.4
3477.075.5
3680.278.7
3883.582.0
4086.985.4
4290.488.8
4494.092.4
4697.696.0
48101.499.8
50105.3103.6
52109.2107.5
54113.3111.6
56117.4115.7
58121.7119.9
60126.0124.2
62130.4128.7
64135.0133.2
66139.7137.8
68144.4142.6
70149.3147.4
72154.3152.4
74159.4157.5
76164.6162.7
78169.9168.0
80175.4173.4
82181.0179.0
84186.7184.7
86192.5190.5
88198.4196.4
90204.5202.4
92210.7208.6
94217.0214.9
96223.5221.4
98230.0228.0
100236.8234.7
102243.6241.5
104250.7248.5
106257.8255.7
108265.1263.0
110272.6270.4
112280.2278.0
114287.9285.8
116295.8293.7
118303.9301.7
120312.1309.9
122320.5318.3
124329.0326.9
126337.7335.6
128346.6344.5
130355.7353.6
132364.9362.8
134374.3372.3
136384.0381.9
138393.7391.7
140403.7401.7
142413.9412.0
144424.3422.4
146434.9433.0
148445.7443.9
150456.8455.0
Saturon app icon

Saturon

All 9 refrigerants on your iPhone, offline in the attic. Superheat, subcooling, target superheat, airflow. $7.99 once.

Get it on the App Store

Other refrigerants

Data: NIST REFPROP-lineage Helmholtz EOS via CoolProp 7.2.0; A2L blends cross-checked vs OEM (Chemours Opteon) glide/pressure anchors. Data version 2026.06.1, pressures in psig at standard sea level (14.696 psia). Reference aid, not a substitute for the manufacturer charging chart. Verify against the equipment nameplate. Published 24 October 2026 by Karolis Valatka, who makes Saturon.